Medical Gas Copper Pipe Fittings

Medical Gas Copper Pipe Fittings

Medical Gas Copper Pipe / Medical Gas Copper Pipe Fittings

Medical gas copper pipe fittings are specially degreased and capped to ensure contaminant-free, high-purity pipeline connections.

  • Description

At Metal Alloys Corporation we proudly manufacture MEDIFLOW BY METALCO marked Medical Grade Copper Pipes used in Medical Gas Distribution system. Uninterrupted Medical Gas supply is a necessity in hospitals (ICCU, Operation Theater, Wards, Nursery etc). Pipes facilitate this in most effective manner.

MEDIFLOW BY METALCO marked medical grade copper tubes are manufactured as per EN13348 / BS EN 1057 specifications. The pipes are manufactured under thorough inspections and quality control measures.

MEDIFLOW BY METALCO marked medical grade copper tubes are available in size range 10mm to 108mm OD, 0.6mm to 2.0mm wall thickness in Half Hard/Hard conditions and Length 3 meter as per requirement.

MEDIFLOW BY METALCO Pipes are subjected to Third Party Inspection agencies like Lloyds, SGS, TUV as per customer demand mandatory specifications and MEDIFLOW BY METALCO.

 

Equivalent Specifications

ParticularStandardMETALCO
CHEMICAL COMPOSITIONCopper (Cu) + Silver (Ag)99.90%Spectro Analysis done per heat as per standard tolerances.
Phosphorous0.015% to 0.04%
CARBON CONTENT TESTDetermining lubricant residue as total Carbon Content by measuring Carbon Dioxide Generated.Tested with Combustion Method as per EN723:2009
TENSILE/ELONGATION TEST
TemperTensile StrengthElongationHardness (Indicative) 
As per EN1773Common TermMPa min.A % minHV 5
R220annealed22040(40 to 75)Specifications maintained with help of In house testing facility.
R250half hard25030(75 to 100)
R290hard2903(min. 100)
DRIFTING TESTDepending on Size and Temper Mandatory/Agreed TermsConical Mandrel @ 45º with tube end expanding 30º
FREE FROM DEFECT TESTEddy Current Test for detection of local defectsEDDY Current Test Conducted in accordance with EN1971
CLEANLINESS REQUIREMENTDegreased, End CapsDegreasing and End caps are fixed at both end of the pipe.
Go Back Top